기본 정보

Principal ClassBOLL
Equipment6.18
PurposeService
Defect Part
PhenomenonThe setting was not applicable and furthermore, some of the filter control function was totally not working. The back flushing sequence was not matched and also not working lamp test function and also not possible sequence working.
Vessel Name<b>GOLAR NANOOK</b>
Hull No2189 FSRU
Order NoREK 498200
EngineerJaesig Seo
Date2018-07-02
Location
SubjectService Report for Sea Water Filter Control on GOLAR NANOOK (Hull No: 2189 FSRU)
ActionInspector Jaesig Seo found that the malfunction was caused by wrong positoned jumper connector. All functions were confirmed good after demonstration and simulation.